Double-skinned corrugated or profiled roof sheeting Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.2 Cavity walls excluded from provisions for cavity barriers. Wording on the drawing: See para 9.3; Close cavity at top of wall (unless cavity is totally filled with insulation); NOTES:; 1. Materials used to close the cavity in this arrangement do not need to achieve a specific performance in relation to fire resistance.; 2. Domestic meter cupboards may be installed provided that the following conditions are met: a. There are no more than two cupboards per dwelling b. The openings in the outer wall leaf are not bigger than; Opening; 800˜500mm for each cupboard c. The inner leaf is not penetrated except by a sleeve not; Close cavity around opening; more than 80˜80mm, which is fire-stopped.; Two leaves of brick or concrete each at least 75mm thick; 3. Materials achieving class B-s3, d2 or worse may be placed within the cavity.