Pathways around fire-separating elements Double-skinned corrugated or profiled roof sheeting

Double-skinned corrugated or profiled roof sheeting

9.8

Cavity barriers are not required between double-skinned corrugated or profiled insulated roof sheeting if the sheeting complies with all of the following.

a. The sheeting is rated class A2-s3, d2 or better.
b. Both surfaces of the insulating layer are rated class C-s3, d2 or better.
c. Both surfaces of the insulating layer make contact with the inner and outer skins of cladding (Diagram 9.4).

Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.2 Cavity walls excluded from provisions for cavity barriers. Wording on the drawing: See para 9.3; Close cavity at top of wall (unless cavity is totally filled with insulation); NOTES:; 1. Materials used to close the cavity in this arrangement do not need to achieve a specific performance in relation to fire resistance.; 2. Domestic meter cupboards may be installed provided that the following conditions are met: a. There are no more than two cupboards per dwelling b. The openings in the outer wall leaf are not bigger than; Opening; 800˜500mm for each cupboard c. The inner leaf is not penetrated except by a sleeve not; Close cavity around opening; more than 80˜80mm, which is fire-stopped.; Two leaves of brick or concrete each at least 75mm thick; 3. Materials achieving class B-s3, d2 or worse may be placed within the cavity.
Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.3 Fire resisting ceiling below cavity. Wording on the drawing: See para 9.5; Floor or roof above; NOTE: The ceiling should meet all of the following conditions. a. Provide a minimum fire resistance of EI 30. b. Be imperforate, except for an opening described in paragraph 9.17. c. Extend throughout the building or compartment. d. Not be easily demountable.; Cavity; Ceiling surface/product exposed to; cavity – class C-s3, d2 or better; Ceiling; So˜t of ceiling – class B-s3, d2 or better
Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting. Wording on the drawing: See para 9.8; Arrangement A Arrangement B; Acceptable without cavity barriers Cavity barriers necessary; Cavity barrier; Insulation; The insulation should make contact with both skins of sheeting. See also Diagram 8.2a regarding the need for fire-stopping where such roofs pass over the top of a compartment wall.
Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting