Pathways around fire-separating elements Double-skinned corrugated or profiled roof sheeting
Double-skinned corrugated or profiled roof sheeting
9.8
Cavity barriers are not required between double-skinned corrugated or profiled insulated roof sheeting if the sheeting complies with all of the following.
a. The sheeting is rated class A2-s3, d2 or better.
b. Both surfaces of the insulating layer are rated class C-s3, d2 or better.
c. Both surfaces of the insulating layer make contact with the inner and outer skins of cladding (Diagram 9.4).
Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting