Double-skinned corrugated or profiled roof sheeting Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.3 Fire resisting ceiling below cavity. Wording on the drawing: See para 9.5; Floor or roof above; NOTE: The ceiling should meet all of the following conditions. a. Provide a minimum fire resistance of EI 30. b. Be imperforate, except for an opening described in paragraph 9.17. c. Extend throughout the building or compartment. d. Not be easily demountable.; Cavity; Ceiling surface/product exposed to; cavity – class C-s3, d2 or better; Ceiling; So˜t of ceiling – class B-s3, d2 or better
Diagram 9.3 Fire resisting ceiling below cavity