Escape route design Division of corridors

Division of corridors

2.26

A corridor providing access to alternative escape route should be divided by fire doorsets fitted with a self-closing device (and associated screens) where both of the following apply.

a. It is more than 12m long.
b. It connects two or more storey exits.

The fire doorsets (including any screens) should be approximately mid-way between the two storey exits. They should safeguard the route from smoke, while considering the layout of the corridor and any adjacent fire risks.

2.27

For buildings other than dwellings (purpose groups 2 to 7): if a cavity exists above the enclosures to a corridor as described above (because the enclosures are not carried to full storey height or the underside of the roof covering at the top storey), the potential for smoke to bypass the enclosure should be restricted by one of the following methods.

a. Method 1 – Fitting cavity barriers on the line of the enclosure(s) to and across the corridor (Diagram 2.9).
b. Method 2 – Dividing the storey using fire resisting construction that passes through the line of the division of the corridor (Diagram 2.9). Any cavity above this division should be fitted with cavity barriers on the line of division of the storey and the corridor.
c. Method 3 – Enclosing the cavity on the lower side by a fire resisting ceiling that extends throughout the building, compartment or separated part.

Any door that could provide a path for smoke to bypass the division should be fitted with a selfclosing device (but need not necessarily be fire resisting).

Diagram 2.9 Division of corridors

Diagram 2.9 Division of corridors. Wording on the drawing: See para 2.27; Method 1 Cavity above ceiling; Method 2 Cavity above ceiling; Cavity barrier; Corridor; Fire resisting construction; Corridor; Fire resisting sub-division; Fd Fire doorset; Fd Fd; Fd; Fd; Floor cavity; Floor cavity; Section A; Section B; Fire resisting construction; Cavity barrier to ceiling cavity; Cavity barrier to ceiling cavity above fire resisting sub-division; Fd; Fd; Cavity barriers on line of corridor enclosure to any cavity above; Fd; Fd; A A B; B; Fire resisting sub-division.; Any cavity above to have cavity barriers; Fd; Fd; NOTES: The sub-division should be carried to full storey For all methods, where the corridor is a protected height and includes sub-division of the escape route, cavity barriers may also be required in corridor. A cavity barrier may be used in any any floor cavity beneath the corridor enclosure ceiling cavity over the sub-division. (see paragraph 9.5).
Diagram 2.9 Division of corridors

2.28

Where dead ends of corridors exceeding 4.5m long provide access to a point from which alternative escape route are available, they should be separated by self-closing fire doorsets (together with any associated screens) from any part of the corridor that either:

a. Provides two directions of escape (Diagram 2.10a)
b. Continues past one storey exit to another (Diagram 2.10b).

Alternatively, the stairs and corridors may be protected by a pressurisation system complying with BS EN 12101-6.

Diagram 2.10 Dead-end corridors exceeding 4.5m long

Diagram 2.10 Dead-end corridors exceeding 4.5m long. Wording on the drawing: See para 2.28; a. ‘T’ junction with b. Continuation main corridor past stairway; Fd Fd; Fd Fd; Fd; Fd Fd Fd Fd Fd Fd; Fd; Fd Fd; Fd Fd; Fd Self-closing fire doorsets; Protected corridor
Diagram 2.10 Dead-end corridors exceeding 4.5m long

View this page on RegsUK