Escape route design Division of corridors
Division of corridors
2.26
A corridor providing access to alternative escape route should be divided by fire doorsets fitted with a self-closing device (and associated screens) where both of the following apply.
The fire doorsets (including any screens) should be approximately mid-way between the two storey exits. They should safeguard the route from smoke, while considering the layout of the corridor and any adjacent fire risks.
2.27
For buildings other than dwellings (purpose groups 2 to 7): if a cavity exists above the enclosures to a corridor as described above (because the enclosures are not carried to full storey height or the underside of the roof covering at the top storey), the potential for smoke to bypass the enclosure should be restricted by one of the following methods.
Any door that could provide a path for smoke to bypass the division should be fitted with a selfclosing device (but need not necessarily be fire resisting).
Diagram 2.9 Division of corridors

2.28
Where dead ends of corridors exceeding 4.5m long provide access to a point from which alternative escape route are available, they should be separated by self-closing fire doorsets (together with any associated screens) from any part of the corridor that either:
Alternatively, the stairs and corridors may be protected by a pressurisation system complying with BS EN 12101-6.
Diagram 2.10 Dead-end corridors exceeding 4.5m long