Methods for calculating acceptable unprotected area Method 2
Method 2
13.20
This method may be used for buildings or compartments intended for any use and for which method 1 is not appropriate.
13.21
Except for an open-sided car park in purpose group 7(b) (see paragraph 11.2), the building should not exceed 10m in height. Each side of the building should meet the limits in Table 13.1. Areas falling within the limits in Diagram 13.5 can be ignored.
Table 13.1 Permitted unprotected areas in small buildings or compartments
| Minimum distance between side of building and relevant boundary (m) | Maximum total percentage of unprotected area (%) (3) | |
|---|---|---|
| Purpose groups | ||
Residential, office, assembly and recreation (1) | Shop and commercial, industrial, storage and other non-residential (2) | |
| Not applicable | 1 | 4 |
| 1 | 2 | 8 |
| 2.5 | 5 | 20 |
| 5 | 10 | 40 |
| 7.5 | 15 | 60 |
| 10 | 20 | 80 |
| 12.5 | 25 | 100 |
NOTES:
1. Intermediate values may be obtained by interpolation.
2. For buildings fitted with an automatic sprinkler system, see paragraph 13.22.
3. For open-sided car parks in purpose group 7(b), the distances set out in column (1) may be used instead of those in column (2).
4. The total percentage of unprotected area is found by dividing the total unprotected area by the area of a rectangle that encloses all the unprotected areas, and multiplying the result by 100.