Method 2 Table 13.1 Permitted unprotected areas in small buildings or compartments
Table 13.1 Permitted unprotected areas in small buildings or compartments
| Minimum distance between side of building and relevant boundary (m) | Maximum total percentage of unprotected area (%) (3) | |
|---|---|---|
| Purpose groups | ||
Residential, office, assembly and recreation (1) | Shop and commercial, industrial, storage and other non-residential (2) | |
| Not applicable | 1 | 4 |
| 1 | 2 | 8 |
| 2.5 | 5 | 20 |
| 5 | 10 | 40 |
| 7.5 | 15 | 60 |
| 10 | 20 | 80 |
| 12.5 | 25 | 100 |
NOTES:
1. Intermediate values may be obtained by interpolation.
2. For buildings fitted with an automatic sprinkler system, see paragraph 13.22.
3. For open-sided car parks in purpose group 7(b), the distances set out in column (1) may be used instead of those in column (2).
4. The total percentage of unprotected area is found by dividing the total unprotected area by the area of a rectangle that encloses all the unprotected areas, and multiplying the result by 100.