Alternative C: Sleeving Table 10.1 Maximum nominal internal diameter of pipes passing through a fire-separating element

Table 10.1 Maximum nominal internal diameter of pipes passing through a fire-separating element

SituationPipe material and maximum nominal internal diameter (mm)

(a)

High melting point metal(1)

(b)

Lead, aluminium, aluminium alloy, uPVC(2), fibrecement

(c)

Any other material

1. Structure (but not a wall separating buildings) enclosing a protected shaft that is not a stairway or a lift shaft
16011040
2. Any other situation
1604040

NOTES:

1. Any metal (such as cast iron, copper or steel) which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flame or hot gas will pass through the wall of the pipe.
2. uPVC pipes that comply with either BS 4514 or BS 5255.