Single escape routes and exits Table 2.1 Limitations on travel distance
Table 2.1 Limitations on travel distance
| Maximum travel distance(1) where travel is possible in: | ||||
|---|---|---|---|---|
| Purpose group | Use of the premises or part of the premises | One direction only (m) | More than one direction (m) | |
| 2(a) | Residential (institutional) | 9 | 18 | |
| 2(b) | Residential (other): | |||
a. in bedrooms(2) | 9 | 18 | ||
b. in bedroom corridors | 9 | 35 | ||
c. elsewhere | 18 | 35 | ||
| 3 | Office | 18 | 45 | |
| 4 | Shop and commercial | 18 | 45 | |
| 5 | Assembly and recreation: | |||
a. buildings primarily for disabled people | 9 | 18 | ||
b. areas with seating in rows | 15 | 32 | ||
c. elsewhere | 18 | 45 | ||
| 6 | Industrial(3) | Normal hazard | 25 | 45 |
| Higher hazard | 12 | 25 | ||
| 7 | Storage and other non-residential(3) | Normal hazard | 25 | 45 |
| Higher hazard | 12 | 25 | ||
| 2–7 | Place of special fire hazard(4) | 9(5) | 18(5) | |
| 2–7 | Plant room or roof-top plant: | |||
a. distance within the room | 9 | 35 | ||
b. escape route not in open air (overall travel distance) | 18 | 45 | ||
c. escape route in open air (overall travel distance) | 60 | 100 | ||
NOTES:
1. If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the actual travel distance.
2. Maximum part of travel distance within the room. This limit applies within the bedroom and any associated dressing room, bathroom or sitting room, etc. The distance is measured to the door to the protected corridor that serves the room or suite. Sub-item (b) applies from that point along the bedroom corridor to a storey exit.
3. In industrial and storage buildings, the appropriate travel distance depends on the level of fire hazard associated with the processes and materials being used.
Higher hazard includes manufacturing, processing or storage of significant amounts of hazardous goods or materials, including any of the following.
• Any compressed, liquefied or dissolved gas.
• Any substance that becomes dangerous by interaction with either air or water.
• Any liquid substance with a flash point below 65°C, including whisky or other alcoholic liquor.
• Any corrosive substance.
• Any oxidising agent.
• Any substance liable to spontaneous combustion.
• Any substance that changes or decomposes readily, giving out heat when doing so.
• Any solid substance with a flash point less than 120°C.
• Any substance that is likely to spread fire by flowing from one part of a building to another.
4. Places of special fire hazard are listed in the definitions in Appendix A.
5. Maximum part of travel distance within the room/area. Travel distance outside the room/area should comply with the limits for the purpose group of the building or part.