Single escape routes and exits Table 2.1 Limitations on travel distance

Table 2.1 Limitations on travel distance

Maximum travel distance(1) where travel is possible in:
Purpose groupUse of the premises or part of the premisesOne direction only (m)More than one direction (m)
2(a)Residential (institutional)918
2(b)Residential (other):
a. in bedrooms(2)
918
b. in bedroom corridors
935
c. elsewhere
1835
3Office1845
4Shop and commercial1845
5Assembly and recreation:
a. buildings primarily for disabled people
918
b. areas with seating in rows
1532
c. elsewhere
1845
6Industrial(3) Normal hazard2545
Higher hazard1225
7Storage and other non-residential(3) Normal hazard2545
Higher hazard1225
2–7Place of special fire hazard(4) 9(5) 18(5)
2–7Plant room or roof-top plant:
a. distance within the room
935
b. escape route not in open air (overall travel distance)
1845
c. escape route in open air (overall travel distance)
60100

NOTES:

1. If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the actual travel distance.
2. Maximum part of travel distance within the room. This limit applies within the bedroom and any associated dressing room, bathroom or sitting room, etc. The distance is measured to the door to the protected corridor that serves the room or suite. Sub-item (b) applies from that point along the bedroom corridor to a storey exit.
3. In industrial and storage buildings, the appropriate travel distance depends on the level of fire hazard associated with the processes and materials being used.
Higher hazard includes manufacturing, processing or storage of significant amounts of hazardous goods or materials, including any of the following.
• Any compressed, liquefied or dissolved gas.
• Any substance that becomes dangerous by interaction with either air or water.
• Any liquid substance with a flash point below 65°C, including whisky or other alcoholic liquor.
• Any corrosive substance.
• Any oxidising agent.
• Any substance liable to spontaneous combustion.
• Any substance that changes or decomposes readily, giving out heat when doing so.
• Any solid substance with a flash point less than 120°C.
• Any substance that is likely to spread fire by flowing from one part of a building to another.
4. Places of special fire hazard are listed in the definitions in Appendix A.
5. Maximum part of travel distance within the room/area. Travel distance outside the room/area should comply with the limits for the purpose group of the building or part.