Width of escape routes and exits Table 2.3 Widths of escape routes and exits

Table 2.3 Widths of escape routes and exits

Maximum number of peopleMinimum width (mm)(1)(2)(3)
60750(4)
110850
2201050
More than 2205 per person(5)

NOTES:

1. See Appendix D for methods of measurement.
2. Widths may need to be increased to meet guidance in Approved Document M.
3. Widths less than 1050mm should not be interpolated.
4. May be reduced to 530mm for gangways between fixed storage racking, other than in public areas of ‘shop and commercial’ (purpose group 4) buildings.
5. 5mm/person does not apply to an opening serving fewer than 220 people.