Escape route design Width of escape routes and exits
Width of escape routes and exits
2.18
The width of escape routes and exits should meet the provisions in Table 2.3, as well as the guidance in Approved Document M.
2.19
If the maximum number of people likely to use the escape route and exit is not known, it should be calculated using the occupant number guidance in Appendix D.
2.20
Guidance on the spacing of fixed seating for auditoria is given in Annex D of BS 9999.
Table 2.3 Widths of escape routes and exits
| Maximum number of people | Minimum width (mm)(1)(2)(3) |
|---|---|
| 60 | 750(4) |
| 110 | 850 |
| 220 | 1050 |
| More than 220 | 5 per person(5) |
NOTES:
1. See Appendix D for methods of measurement.
2. Widths may need to be increased to meet guidance in Approved Document M.
3. Widths less than 1050mm should not be interpolated.
4. May be reduced to 530mm for gangways between fixed storage racking, other than in public areas of ‘shop and commercial’ (purpose group 4) buildings.
5. 5mm/person does not apply to an opening serving fewer than 220 people.