Simultaneous evacuation Table 3.2 Capacity of stairs for basements and for simultaneous evacuation of the building
Table 3.2 Capacity of stairs for basements and for simultaneous evacuation of the building
| No. of floors served | Maximum number of people served by a stair of width: | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| 1000mm | 1100mm | 1200mm | 1300mm | 1400mm | 1500mm | 1600mm | 1700mm | 1800mm | |
| 1 | 150 | 220 | 240 | 260 | 280 | 300 | 320 | 340 | 360 |
| 2 | 190 | 260 | 285 | 310 | 335 | 360 | 385 | 410 | 435 |
| 3 | 230 | 300 | 330 | 360 | 390 | 420 | 450 | 480 | 510 |
| 4 | 270 | 340 | 375 | 410 | 445 | 480 | 515 | 550 | 585 |
| 5 | 310 | 380 | 420 | 460 | 500 | 540 | 580 | 620 | 660 |
| 6 | 350 | 420 | 465 | 510 | 555 | 600 | 645 | 690 | 735 |
| 7 | 390 | 460 | 510 | 560 | 610 | 660 | 710 | 760 | 810 |
| 8 | 430 | 500 | 555 | 610 | 665 | 720 | 775 | 830 | 885 |
| 9 | 470 | 540 | 600 | 660 | 720 | 780 | 840 | 900 | 960 |
| 10 | 510 | 580 | 645 | 710 | 775 | 840 | 905 | 970 | 1035 |
NOTES:
1. The capacity of stairs that serve more than 10 storeys may be obtained by using linear extrapolation.
2. The capacity of stairs not less than 1100mm wide may also be obtained by using the formulas in paragraph 3.18.
3. Unless a central handrail is provided, stairs with a rise of more than 30m should be a maximum width of 1400mm (see paragraph 3.10).
4. Stairs wider than 2000mm should have a central handrail (see paragraph 3.11).