Phased evacuation Table 3.3 Minimum width of stairs designed for phased evacuation
Table 3.3 Minimum width of stairs designed for phased evacuation
| Maximum number of people in any storey | Stair width (mm) |
|---|---|
| 100 | 1000 |
| 120 | 1100 |
| 130 | 1200 |
| 140 | 1300 |
| 150 | 1400 |
| 160 | 1500 |
| 170 | 1600 |
| 180 | 1700 |
| 190 | 1800 |
NOTES:
1. This table assumes a phased evacuation of the fire floor first followed by evacuation of not more than two floors at a time.
2. Unless a central handrail is provided, stairs with a rise of more than 30m should be a maximum width of 1400mm (see paragraph 3.10).
3. As an alternative to using this table, the minimum width (in mm) may be calculated from: (P×10) – 100 where P = the number of people on the most heavily occupied storey. However, the minimum width of a stair should be 1000mm.