Buildings containing one or more atria Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)

Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)

Purpose group of building or partHeight of floor of top storey above ground level (m)Maximum floor area of any one storey in the building or any one storey in a compartment (m2)
Single storey buildingsMulti-storey buildings
OfficeNo limit(1) No limitNo limit
Assembly and recreation, shop and commercial:
a. Shops – without sprinkler system
No limit(1) 20002000
Shops – with sprinkler system(2) No limitNo limit4000
b. Elsewhere – without sprinkler system
No limit(1) No limit2000
Elsewhere – with sprinkler system(2) No limitNo limit4000
Industrial(3)
Without sprinkler system(1) Not more than 18No limit7000
More than 18N/A2000(4)
With sprinkler system(2) Not more than 18No limit14,000
More than 18N/A4000(4)
Height of floor of top storey above ground level (m)Maximum floor area (m2)Maximum height (m)(5) Maximum compartment volume (m3)
Single storey buildingsMulti-storey buildings
Storage(3) and other non-residential:
a. Car park for light vehicles
No limitNo limitNo limitNo limit
b. Any other building or part:
Without sprinkler system(1) Not more than 1820,0001820,000
More than 18N/AN/A4000(4)
With sprinkler system(2) Not more than 18No limitNo limit40,000
More than 188000(4)

NOTES:

This table recommends that where the maximum size limitations placed on a building without a sprinkler system are exceeded, a sprinkler system in accordance with Appendix E should be provided.

1. See Appendix B, Table B2 for sprinkler system height requirements.
2. ‘With sprinkler system’ means that the building is fitted throughout with an automatic sprinkler system in accordance with Appendix E.
3. In certain industrial and storage uses that are subject to other legislation, for example the storage of LPG and certain chemicals, additional limitations on floor area and/or additional sprinkler provisions might apply.
4. This reduced limit applies only to storeys that are a minimum of 18m above ground level. Below this height the higher limit applies.
5. Compartment height is measured from finished floor level to the underside of the roof or ceiling.