Provision of compartmentation Buildings containing one or more atria

Buildings containing one or more atria

8.13

Detailed advice on atria in buildings is given in Annexes B and C of BS 9999. For the purposes of this document, BS 9999 applies only where the atrium breaches a compartment.

Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11. Wording on the drawing: See para 8.11; b. Compartmentation in buildings over 30m see paragraph 8.11b Compartment floor(s) or wall(s); a. Example of compartmentation in an unsprinklered assembly and recreation, shop, or commercial building see paragraph 8.11a; > 30m; Storey not exceeding; 2000m²; Storey not exceeding; Roof; 2000m²; 30m max.; Storey exceeding 2000m² divided by compartment wall; Compartment; wall; Storey exceeding 2000m² divided by compartment wall; Compartment; wall; None of the floors in this case would need to be compartment floors, but the two storeys exceeding 2000m² would need to be divided into compartments not more than 2000m² by compartment walls.; In a building with a top storey over 30m in height all storeys should be separated by compartment floors. For advice on the special conditions in atrium buildings see Annex B of BS 9999.; The compartment walls in example (a) do not need to be in one vertical plane.; d. Deep basement see paragraph 8.11d; c. Shallow basement see paragraph 8.11c; > 10m; 10m max.; Only the floor of the ground storey need be a compartment floor if the lower basement is at a depth of not more than 10m.; All basement storeys to be separated by compartment floors if any storey is at a depth of more than 10m.
Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)

Purpose group of building or partHeight of floor of top storey above ground level (m)Maximum floor area of any one storey in the building or any one storey in a compartment (m2)
Single storey buildingsMulti-storey buildings
OfficeNo limit(1) No limitNo limit
Assembly and recreation, shop and commercial:
a. Shops – without sprinkler system
No limit(1) 20002000
Shops – with sprinkler system(2) No limitNo limit4000
b. Elsewhere – without sprinkler system
No limit(1) No limit2000
Elsewhere – with sprinkler system(2) No limitNo limit4000
Industrial(3)
Without sprinkler system(1) Not more than 18No limit7000
More than 18N/A2000(4)
With sprinkler system(2) Not more than 18No limit14,000
More than 18N/A4000(4)
Height of floor of top storey above ground level (m)Maximum floor area (m2)Maximum height (m)(5) Maximum compartment volume (m3)
Single storey buildingsMulti-storey buildings
Storage(3) and other non-residential:
a. Car park for light vehicles
No limitNo limitNo limitNo limit
b. Any other building or part:
Without sprinkler system(1) Not more than 1820,0001820,000
More than 18N/AN/A4000(4)
With sprinkler system(2) Not more than 18No limitNo limit40,000
More than 188000(4)

NOTES:

This table recommends that where the maximum size limitations placed on a building without a sprinkler system are exceeded, a sprinkler system in accordance with Appendix E should be provided.

1. See Appendix B, Table B2 for sprinkler system height requirements.
2. ‘With sprinkler system’ means that the building is fitted throughout with an automatic sprinkler system in accordance with Appendix E.
3. In certain industrial and storage uses that are subject to other legislation, for example the storage of LPG and certain chemicals, additional limitations on floor area and/or additional sprinkler provisions might apply.
4. This reduced limit applies only to storeys that are a minimum of 18m above ground level. Below this height the higher limit applies.
5. Compartment height is measured from finished floor level to the underside of the roof or ceiling.