Fire resistance Table B1 Specific provisions of the test for fire resistance of elements of structure, etc.
Table B1 Specific provisions of the test for fire resistance of elements of structure, etc.
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment).
| Part of building | Minimum provisions when tested to the relevant European standard (minutes)(1) | Alternative minimum provisions when tested to the relevant part of BS 476(2) (minutes) | Type of exposure | ||
|---|---|---|---|---|---|
| Loadbearing capacity(3) | Integrity | Insulation | |||
1. Structural frame, beam or column. | R see Table B2 | See Table B2 | Not applicable | Not applicable | Exposed faces |
2. Loadbearing wall (for a wall which is also described in any of the following items, the more onerous guidance should be applied). | R see Table B2 | See Table B2 | Not applicable | Not applicable | Each side separately |
3. Floors(4) | |||||
a. between a shop and flat above | REI 60 or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | From underside(5) |
b. in upper storey of two storey dwellinghouse (but not over garage or basement) | R 30 and EI 15 | 30 min | 15 min | 15 min | From underside(5) |
c. any other floor – including compartment floors. | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | From underside(5) |
4. Roofs | |||||
a. any part forming an escape route | REI 30 | 30 min | 30 min | 30 min | From underside(5) |
b. any roof that performs the function of a floor. | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | From underside(5) |
5. External walls | |||||
a. any part a maximum of 1000mm from any point on the relevant boundary(6) | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | Each side separately |
b. any part a minimum of 1000mm from the relevant boundary(6) | RE see Table B2 and I 15 | See Table B2 | See Table B2 | 15 min | From inside the building |
c. any part beside an external escape route (Section 2 Diagram 2.7 of Approved Document B Volume 1 and Section 3, Diagram 3.4). | RE 30 | 30 min | 30 min | No provision(7) (8) | From inside the building |
6. Compartment walls Separating either: | |||||
a. a flat from any other part of the building (see paragraph 7.1 of Approved Document B Volume 1) | REI 60 or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
b. occupancies. | REI 60 or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
7. Compartment walls (other than in item 6 or item 10). | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | Each side separately |
8. Protected shafts Excluding any firefighting shaft: | |||||
a. any glazing described in Section 8 diagram 8.4 | E 30 | Not applicable | 30 min | No provision(8) | Each side separately |
b. any other part between the shaft and a protected lobby/corridor described in Section 8 diagram 8.4 | REI 30 | 30 min | 30 min | 30 min | Each side separately |
c. any part not described in (a) or (b) above. | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | Each side separately |
9. Enclosure (that does not form part of a compartment wall or a protected shaft) to a: | |||||
a. protected stairway | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
b. lift shaft. | REI 30 | 30 min | 30 min | 30 min | Each side separately |
10. Wall or floor separating an attached or integral garage from a dwellinghouse | REI 30(8) | 30 min | 30 min | 30 min(8) | From garage side |
11. Fire resisting construction in dwellinghouses not described elsewhere | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
12. Firefighting shafts | REI 120 | 120 min | 120 min | 120 min | From side remote from shaft |
a. construction that separates firefighting shaft from rest of building | REI 60 | 60 min | 60 min | 60 min | From shaft side |
b. construction that separates firefighting stair, firefighting lift shaft and firefighting lobby. | REI 60 | 60 min | 60 min | 60 min | Each side separately |
13. Enclosure (that is not a compartment wall or described in item 8) to a: | |||||
a. protected lobby | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
b. protected corridor. | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
14. Sub-division of a corridor | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
15. Fire resisting construction | |||||
a. construction that encloses places of special fire hazard | REI 30 | 30 min | 30 min | 30 min | Each side separately |
b. construction between store rooms and sales area in shops | REI 30 | 30 min | 30 min | 30 min | Each side separately |
c. fire resisting sub-division | REI 30 | 30 min | 30 min | 30 min | Each side separately |
d. construction that encloses bedrooms and ancillary accommodation in care homes. | REI 30 | 30 min | 30 min | 30 min | Each side separately |
16. Enclosure in a flat to a protected entrance hall, or to a protected landing. | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
17. Cavity barrier | E 30 and I 15 | Not applicable | 30 min | 15 min | Each side separately |
18. Ceiling see paragraph 2.5, Diagram 2.3 of Approved Document B Volume 1 and paragraph 9.5 and Diagram 9.3. | EI 30 | Not applicable | 30 min | 30 min | From underside |
19. Duct described in paragraph 9.17e. | E 30 | Not applicable | 30 min | No provision | From outside |
20. Casing around a drainage system described in Diagram 9.1 of Approved Document B Volume 1. | E 30 | Not applicable | 30 min | No provision | From outside |
21. Flue walls described in Diagram 10.4. | EI half the period given in Table B2 for the compartment wall/floor | Not applicable | Half the period given in Table B2 for the compartment wall/floor | Half the period given in Table B2 for the compartment wall/floor | From outside |
22. Construction described in note (a) to paragraph 12.9 of Approved Document B Volume 1. | EI 30 | Not applicable | 30 min | 30 min | From underside |
23. Fire doorsets | See Table C1 | See Table C1 | See Appendix C | ||
NOTES:
1. BS EN 13501-2 Classification using data from fire resistance tests, excluding ventilation services. BS EN 13501-3 Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers. BS EN 13501-4 Classification using data from fire resistance tests on components of smoke control systems.
In the European classification:
‘R’ is the resistance to fire in terms of loadbearing capacity.
‘E’ is the resistance to fire in terms of integrity.
‘I’ is the resistance to fire in terms of insulation.
The national classifications do not automatically equate with the alternative classifications in the European column, therefore products cannot typically assume a European class unless they have been tested accordingly.
2. BS 476-20 for general principles, BS 476-21 for loadbearing elements, BS 476-22 for non-loadbearing elements, BS 476-23 for fire-protecting suspended ceilings and BS 476-24 for ventilation ducts.
3. Applies to loadbearing elements only (see paragraph B19).
4. Guidance on increasing the fire resistance of existing timber floors is given in BRE Digest 208.
5. Only if a suspended ceiling meets the appropriate provisions should it be relied on to add to the fire resistance of the floor.
6. Such walls may contain areas that do not need to be fire resisting (unprotected areas). See Section 13.
7. Unless needed as part of a wall in item 5a or 5b.
8. Except for any limitations on uninsulated glazed elements given in Table B3.