Fire resistance (2029 amendment) Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment)
Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B1 Specific provisions of the test for fire resistance of elements of structure, etc..
| Part of building | Minimum provisions when tested and classified to the relevant European standard (minutes)(1) or assessed following the recommendations of paragraphs B1 to B5 (minutes)(2) | Type of exposure | ||
|---|---|---|---|---|
| Loadbearing capacity(3) | Integrity | Insulation | ||
1. Structural frame, beam or column. | See Table B2 | Not applicable | Not applicable | Exposed faces |
2. Loadbearing wall (for a wall which is also described in any of the following items, the more onerous guidance should be applied). | See Table B2 | Not applicable | Not applicable | Each side separately |
3. Floors(4) | ||||
a. between a shop and flat above | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | From underside(5) |
b. in upper storey of two storey dwellinghouse (but not over garage or basement) | 30 min | 15 min | 15 min | From underside (5) |
c. any other floor – including compartment floors. | See Table B2 | See Table B2 | See Table B2 | From underside (5) |
4. Roofs | ||||
a. any part forming an escape route | 30 min | 30 min | 30 min | From underside (5) |
b. any roof that performs the function of a floor. | See Table B2 | See Table B2 | See Table B2 | From underside (5) |
5. External walls | ||||
a. any part a maximum of 1000mm from any point on the relevant boundary(6) | See Table B2 | See Table B2 | See Table B2 | Each side separately |
b. any part a minimum of 1000mm from the relevant boundary(6) | See Table B2 | See Table B2 | 15 min | From inside the building |
c. any part beside an external escape route (Section 2, Diagram 2.7 of Approved Document B Volume 1 and Section 3, Diagram 3.4). | 30 min | 30 min | No provision(7) (8) | From inside the building |
6. Compartment walls Separating either: | ||||
a. a flat from any other part of the building (see paragraph 7.1 of Approved Document B Volume 1) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
b. occupancies. | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
7. Compartment walls (other than in item 6 or item 10). | See Table B2 | See Table B2 | See Table B2 | Each side separately |
8. Protected shafts Excluding any firefighting shaft: | ||||
a. any glazing described in Section 8, Diagram 8.4 | Not applicable | 30 min | No provision(8) | Each side separately |
b. any other part between the shaft and a protected lobby/corridor described in Section 8, Diagram 8.4 | 30 min | 30 min | 30 min | Each side separately |
c. any part not described in (a) or (b) above. | See Table B2 | See Table B2 | See Table B2 | Each side separately |
9. Enclosure (that does not form part of a compartment wall or a protected shaft) to a: | ||||
a. protected stairway | 30 min | 30 min | 30 min(8) | Each side separately |
b. lift shaft. | 30 min | 30 min | 30 min | Each side separately |
10. Wall or floor separating an attached or integral garage from a dwellinghouse | 30 min | 30 min | 30 min(8) | From garage side |
11. Fire resisting construction in dwellinghouses not described elsewhere | 30 min | 30 min | 30 min(8) | Each side separately |
12. Firefighting shafts | 120 min | 120 min | 120 min | From side remote from shaft |
a. construction that separates firefighting shaft from rest of building | 60 min | 60 min | 60 min | From shaft side |
b. construction that separates firefighting stair, firefighting lift shaft and firefighting lobby. | 60 min | 60 min | 60 min | Each side separately |
13. Enclosure (that is not a compartment wall or described in item 8) to a: | ||||
a. protected lobby | 30 min | 30 min | 30 min(8) | Each side separately |
b. protected corridor. | 30 min | 30 min | 30 min(8) | Each side separately |
14. Sub-division of a corridor | 30 min | 30 min | 30 min(8) | Each side separately |
15. Fire resisting construction | ||||
a. construction that encloses places of special fire hazard | 30 min | 30 min | 30 min | Each side separately |
b. construction between store rooms and sales area in shops | 30 min | 30 min | 30 min | Each side separately |
c. fire resisting sub-division | 30 min | 30 min | 30 min | Each side separately |
d. construction that encloses bedrooms and ancillary accommodation in care homes. | 30 min | 30 min | 30 min | Each side separately |
16. Enclosure in a flat to a protected entrance hall, or to a protected landing. | 30 min | 30 min | 30 min(8) | Each side separately |
17. Cavity barrier | Not applicable | 30 min | 15 min | Each side separately |
18. Ceiling see see paragraph 2.5, Diagram 2.3 of Approved Document B Volume 1 and paragraph 9.5 and Diagram 9.3. | Not applicable | 30 min | 30 min | From underside |
19. Duct described in paragraph 9.17e. | Not applicable | 30 min | No provision | From outside |
20. Casing around a drainage system described in Diagram 9.1 of Approved Document B Volume 1. | Not applicable | 30 min | No provision | From outside |
21. Flue walls described in Diagram 10.4. | Not applicable | Half the period given in Table B2 for the compartment wall/floor | Half the period given in Table B2 for the compartment wall/floor | From outside |
22. Construction described in note (a) to paragraph 12.9 of Approved Document B Volume 1. | Not applicable | 30 min | 30 min | From underside |
23. Fire doorsets | See Table C1 | See Appendix C | ||
NOTES:
1. Classified in accordance with BS EN 13501-2, BS EN 13501-3 or BS EN 13501-4. In the European classification ‘R’ is the resistance to fire in terms of loadbearing capacity, ‘E’ is the resistance to fire in terms of integrity, ‘I’ is the resistance to fire in terms of insulation. Products or systems cannot typically assume a European class unless they have been tested and classified accordingly.
2. When assessed as being capable of meeting a performance classification, products or systems should follow the relevant test standards to indicate their fire resistance performance in terms of loadbearing capacity, integrity or insulation for a period of minutes, when following the recommendations of paragraphs B1 to B5.
3. Applies to loadbearing elements only (see paragraph B18).
4. Guidance on increasing the fire resistance of existing timber floors is given in BRE Digest 208.
5. Only if a suspended ceiling meets the appropriate provisions should it be relied on to add to the fire resistance of the floor.
6. Such walls may contain areas that do not need to be fire resisting (unprotected areas). See Section 13.
7. Unless needed as part of a wall in item 5a or 5b.
8. Except for any limitations on uninsulated glazed elements given in Table B3.