Fire resistance (2029 amendment) Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment)

Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B1 Specific provisions of the test for fire resistance of elements of structure, etc..

Part of buildingMinimum provisions when tested and classified to the relevant European standard (minutes)(1) or assessed following the recommendations of paragraphs B1 to B5 (minutes)(2) Type of exposure
Loadbearing capacity(3) IntegrityInsulation
1. Structural frame, beam or column.
See Table B2Not applicableNot applicableExposed faces
2. Loadbearing wall
(for a wall which is also described in any of the following items, the more onerous guidance should be applied).
See Table B2Not applicableNot applicableEach side separately
3. Floors(4)
a. between a shop and flat above
60 min or see Table B2 (whichever is greater)60 min or see Table B2 (whichever is greater)60 min or see Table B2 (whichever is greater)From underside(5)
b. in upper storey of two storey dwellinghouse (but not over garage or basement)
30 min15 min15 minFrom underside (5)
c. any other floor – including compartment floors.
See Table B2See Table B2See Table B2From underside (5)
4. Roofs
a. any part forming an escape route
30 min30 min30 minFrom underside (5)
b. any roof that performs the function of a floor.
See Table B2See Table B2See Table B2From underside (5)
5. External walls
a. any part a maximum of 1000mm from any point on the relevant boundary(6)
See Table B2See Table B2See Table B2Each side separately
b. any part a minimum of 1000mm from the relevant boundary(6)
See Table B2See Table B215 minFrom inside the building
c. any part beside an external escape route (Section 2, Diagram 2.7 of Approved Document B Volume 1 and Section 3, Diagram 3.4).
30 min30 minNo provision(7) (8) From inside the building
6. Compartment walls Separating either:
a. a flat from any other part of the building (see paragraph 7.1 of Approved Document B Volume 1)
60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)Each side separately
b. occupancies.
60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)Each side separately
7. Compartment walls (other than in item 6 or item 10).
See Table B2See Table B2See Table B2Each side separately
8. Protected shafts
Excluding any firefighting shaft:
a. any glazing described in Section 8, Diagram 8.4
Not applicable30 minNo provision(8) Each side separately
b. any other part between the shaft and a protected lobby/corridor described in Section 8, Diagram 8.4
30 min30 min30 minEach side separately
c. any part not described in (a) or (b) above.
See Table B2See Table B2See Table B2Each side separately
9. Enclosure (that does not form part of a compartment wall or a protected shaft) to a:
a. protected stairway
30 min30 min30 min(8) Each side separately
b. lift shaft.
30 min30 min30 minEach side separately
10. Wall or floor separating an attached or integral garage from a dwellinghouse
30 min30 min30 min(8) From garage side
11. Fire resisting construction in dwellinghouses not described elsewhere
30 min30 min30 min(8) Each side separately
12. Firefighting shafts
120 min120 min120 minFrom side remote from shaft
a. construction that separates firefighting shaft from rest of building
60 min60 min60 minFrom shaft side
b. construction that separates firefighting stair, firefighting lift shaft and firefighting lobby.
60 min60 min60 minEach side separately
13. Enclosure (that is not a compartment wall or described in item 8) to a:
a. protected lobby
30 min30 min30 min(8) Each side separately
b. protected corridor.
30 min30 min30 min(8) Each side separately
14. Sub-division of a corridor
30 min30 min30 min(8) Each side separately
15. Fire resisting construction
a. construction that encloses places of special fire hazard
30 min30 min30 minEach side separately
b. construction between store rooms and sales area in shops
30 min30 min30 minEach side separately
c. fire resisting sub-division
30 min30 min30 minEach side separately
d. construction that encloses bedrooms and ancillary accommodation in care homes.
30 min30 min30 minEach side separately
16. Enclosure in a flat to a protected entrance hall, or to a protected landing.
30 min30 min30 min(8) Each side separately
17. Cavity barrier
Not applicable30 min15 minEach side separately
18. Ceiling see see paragraph 2.5, Diagram 2.3 of Approved Document B Volume 1 and paragraph 9.5 and Diagram 9.3.
Not applicable30 min30 minFrom underside
19. Duct described in paragraph 9.17e.
Not applicable30 minNo provisionFrom outside
20. Casing around a drainage system described in Diagram 9.1 of Approved Document B Volume 1.
Not applicable30 minNo provisionFrom outside
21. Flue walls described in Diagram 10.4.
Not applicableHalf the period given in Table B2 for the compartment wall/floorHalf the period given in Table B2 for the compartment wall/floorFrom outside
22. Construction described in note
(a) to paragraph 12.9 of Approved Document B Volume 1.
Not applicable30 min30 minFrom underside
23. Fire doorsets
See Table C1See Appendix C

NOTES:

1. Classified in accordance with BS EN 13501-2, BS EN 13501-3 or BS EN 13501-4. In the European classification ‘R’ is the resistance to fire in terms of loadbearing capacity, ‘E’ is the resistance to fire in terms of integrity, ‘I’ is the resistance to fire in terms of insulation. Products or systems cannot typically assume a European class unless they have been tested and classified accordingly.
2. When assessed as being capable of meeting a performance classification, products or systems should follow the relevant test standards to indicate their fire resistance performance in terms of loadbearing capacity, integrity or insulation for a period of minutes, when following the recommendations of paragraphs B1 to B5.
3. Applies to loadbearing elements only (see paragraph B18).
4. Guidance on increasing the fire resistance of existing timber floors is given in BRE Digest 208.
5. Only if a suspended ceiling meets the appropriate provisions should it be relied on to add to the fire resistance of the floor.
6. Such walls may contain areas that do not need to be fire resisting (unprotected areas). See Section 13.
7. Unless needed as part of a wall in item 5a or 5b.
8. Except for any limitations on uninsulated glazed elements given in Table B3.